ATyS g M - 542933D - SOCOMEC
14
EN
FT
STEP 5
Programming
Check
STEP 6A
Automatic operation
Close the front cover as shown to put the
product into automatic mode.
STEP 4
Whilst in manual mode, check the
wiring and if ok power up the
product.
STEP 6C
Padlocking mode
•
In order to padlock put the product in
manual mode.
•
Pull the locking mecha nism and insert
a padlock as shown.
•
As standard padlocking in the 0 position.
Configurable to I-0-II (see step 1).
STEP 6B
Manual operation
•
Open the front cover as shown to put
into manual mode.
•
Use the handle situated in the front
panel under the cover to operate the
transfer switch.
•
Check the changeover switch position
on the indicator before operating.
To simplify operation
use the handle with the
extension provided.
(Max 8 Nm)
II
I
o
0,5 to 2,5 mm
2
#28 to #14 AWG
0,5 to 2,5 mm
2
#28 to #14 AWG
6 mm / 0,236"
Slotted head 2,5 mm
90º
90º
Extension
1x 4-8 mm
The LED signalling and operation is only active when the product supply is available.
To set the dip switches, it is necessary to open the Auto/Manual cover.
Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the defined thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
Source LED ON
LED OFF LED blinking
Source 1
available
Source 1
missing or
out of
range
- a timer is
counting
down
- test mode
Source 2
available
Source 2
missing or
out of
range
- a timer is
counting
down
Source availability LED
•
E: No stop in O position
•
F: 2s stop in O position
Stop in 0 position: E-F
•
C: 50 Hz
•
D: 60 Hz
Frequency: C-D
•
A: 3P
•
B: 1P
Type of network: A-B
•
G: Network - Genset
•
H: Network - Network
Type of application: G-H
HYST: 20 %
D
U/F
D
U: 5-20%
D
F: 3-10%
Dip switch settings
Led info
A
Source voltage
supply configuration
B
Loss of priority source timer
127/230 Vac version 230/400 Vac version
Un (P-P):
208-240 Vac
Un (P-N):
120-138 Vac
Un (P-P):
380-420 Vac
Un (P-N):
220-240 Vac
FT: 0-30 sec.
U/F
[HYST]
[HYST]
RT: 0-30 min.
U/F
Timer settings
C
D
Fault reset
Return of priority source timer
LED ON
LED OFF LED blinking
Fault
Product OK Wait
Auto mode Manual
mode
Manual
retransfer
Fault and state of the product Leds
RT
Содержание ATyS g M