9. INSTALLATION OF OPTIONAL ACCESSORIES
9.1.
Auxilliary contacts
Ref. 1309 1001 or ref. 1309 1011.
To fit an additional AC, the switch must first be put in the 0 position. An auxiliary contact module comprises: one NO/NC
or NOC changeover contact for each position (I-0-II). To install use the screws supplied with the module.
One module is factory fitted.
10 mm
0,5 to 2.5 mm²
solid
stranded
0,5 to 1.5 mm²
PUSH-IN
Use 20mm
screws for
1 module
Use 35mm
screws for
2 modules
Posidriv PZ2
1 Nm
9.2.
Voltage sensing and power supply tap
Ref. 1399 4006.
This provides 2 connection terminals for conductors with cross-section ≤ 1.5 mm².
The single pole terminals can be fitted in any of the terminal cages without reducing the cage connection capacity.
2 parts/ref. Do not use in case of use of the bridging bar.
6 mm
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
9.3.
Bridging bars 2P
Ratings ≤ 125A: ref. 1309 2006; 160A : ref. 1309 2016
10 to
70 mm²
15mm
Hexagonal Metric
Allen size 4
5,0 Nm
Bridging bar.
125A: 1309 2006
160A: 1309 2016
OK
OK
OK
OK
Allen size 4
Hexagonal Metric
44.1 lb-in
5,0 Nm
15 mm /
0,59 "
# 8 to # 00 AWG
10 to 70 mm
2
10 to 70 mm
2
*
# 8 to # 00 AWG
!
X4
OK
OK
OK
OK
Allen size 4
Hexagonal Metric
44.1 lb-in
5,0 Nm
15 mm /
0,59 "
# 8 to # 00 AWG
10 to 70 mm
2
10 to 70 mm
2
*
# 8 to # 00 AWG
!
X4
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
/
317 315 314 313
201
202
102 101
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
/
317 315 314 313
201
202
102 101
OK
NOK
Source II
LOAD
Make sure that the bridging bar is fitted to the correct set of terminals.
There are two references available: one for ratings up to 125A, and another for 160A rating.