3-2. Wiring
3-2-1. Connection Circuit
Wire power cables according to the connection circuit and wiring chart.
Make sure to ground the ground terminal with a ground resistance of 100Ω or less.
The ground terminal is used as a reference electric potential for static neutralization. If the ground terminal is
not grounded, the Ionizer will not be able to achieve the optimal offset voltage (ion balance).
Connection circuit
NPN Input / Output
Be sure to ground.
+24V
+24V
+24V
+24V
Power supply
24 VDC
+24V
0V
F.G.
Brown
+24 VDC
Blue
0V
Orange
Discharge stop signal
Pink
Reset signal
Grey
External switch signal 1
Light blue External switch signal 2
White
Discharge signal
Purple
Error signal
Yellow
Maintenance signal
+24V
Be sure to ground.
Ground terminal
INPUT
OUTPUT
OUTPUT
INPUT
PLC
or
or
or
or
Inte
rna
l c
ircui
t
The product