Chapter 3 Alarm Indication and Troubleshooting
3.3 Troubleshooting
HRS Series
3-82
6.
Check for an input to the pressure sensor in the refrigerant circuit.
Check that the power is supplied to the refrigerant circuit pressure sensor.
Check voltage by contacting the probe of the tester directly to the connector external surface with
the "CN4" connector of the main board being inserted.
<Refrigerant circuit pressure sensor (for low pressure)>
Contact the positive probe to the pin number 24 and contact the negative probe to the pin number
12 of the "CN4" connector.
<Normal> Pin number 24 - Pin number 12: Voltage should be 5 VDC +/- 1V
Fig. 3.3-58 Check of the refrigerant circuit pressure sensor (for low pressure) input