HRX-MM-N007
Chapter 4 Service Procedure
4.5 Replacement Procedure
HRS Series
4-32
Be sure to shut off the bre
aker of the facility power supply (the user’s
machine power supply) before replacement work.
4.5.8
Replacement of pressure sensor
<
HRS
-A/W-
>
Table 4-15 Part number of service parts (Pressure sensor)
Description
Part number
Pressure sensor (For circulating fluid)
HRS-S0011
Removal
1.
Remove the upper panel and the side panel on the right referring the 4.2.1 Removal and the
mounting of the panel.
2.
Remove the connector of the pressure sensor cable (PS1) from the pressure sensor.
3.
Remove the pressure sensor.
Fig. 4.5-16 Removal of pressure sensor
Mounting
1.
Apply a liquid gasket to the threads of the pressure sensor and mount it.
2.
Mount the connector or the pressure sensor cable (PS1) to the pressure sensor.
3.
Mount the upper panel and the side panel on the right in reversed order of removal.
2.
Connector
3.
Pressure sensor