HRX-MM-N007
Chapter 3 Alarm Indication and Troubleshooting
HRS Series
3.3 Troubleshooting
3-53
6.
Check the pressure sensor in the refrigerant circuit.
Two pressure sensors, one for high pressure and the other for low pressure, are used for the
refrigerant circuit. Take the following instructions to check for any abnormality with the pressure
sensors:
(1) Stop the Thermo-Chiller operation.
(2) Check the temperature shown for "Ph: Refrigerant circuit pressure on the high pressure side"
and "PL: Refrigerant circuit pressure on the low pressure side" in the "Check Monitor Menu".
(3) If the pressure value shown by each sensor is +/- 0.1 MPa (Ph = PL +/- 0.1), it means that the
pressure sensors are operating correctly.
7.
Check for an input to the pressure sensor in the refrigerant circuit.
Check that the power is supplied to the refrigerant circuit pressure sensor.
Check voltage by contacting the probe of the tester directly to the connector external surface with
the "CN4" connector of the main board being inserted.
<Refrigerant circuit pressure sensor (for low pressure)>
Contact the positive probe to the pin number 24 and contact the negative probe to the pin number
12 of the "CN4" connector.
<Normal> Pin number 24 - Pin number 12: Voltage should be 5 VDC +/- 1V
Fig. 3.3-29 Check of the refrigerant circuit pressure sensor (for low pressure) input
Содержание HRS012-A*-10-*
Страница 16: ...HRX MM N007 Chapter 2 Name of Parts 2 2 Component Parts HRS Series 2 4...
Страница 136: ...HRX MM N007 Chapter 3 Alarm Indication and Troubleshooting 3 3 Troubleshooting HRS Series 3 120...
Страница 200: ...HRX MM N007 Chapter 4 Service Procedure 4 5 Replacement Procedure HRS Series 4 64...
Страница 220: ...HRX MM N007 Chapter 6 Documents 6 4 Flow chart HRS Series 6 8...