HRX-MM-N007
Chapter 3 Alarm Indication and Troubleshooting
3.3 Troubleshooting
HRS Series
3-34
AL06: High circulating fluid discharge pressure
<Detection method> This alarm goes off when the pressures detected by the circulating fluid pressure
sensor (for discharge) reach the following values.
- Standard pump: The alarm will not be generated.
- Option T (High pressure pump): 0.70 MPa
- Option MT (High pressure pump for pure water): 0.60 MPa
4.
Does AL25 go off when
the circulating fluid pressure
sensor connector is
disconnected?
N
High circulating fluid discharge
pressure
AL06
Is AL25 being generated?
Y
N
Y
N
Are other alarms being
generated simultaneously?
Y
Check the troubleshooting
that is corresponding to the
alarm number that is being
generated.
Refer to the section "AL25:
Circulating fluid discharge
pressure sensor failure".
1.
Check the external piping.
Error
Remove any causes of the
problems.
Is the pump high
pressure pump?
2.
Check the operating time of
the Thermo-Chiller.
Error
External piping resistance is
too large.
Connect a by-pass piping.
Normal
Normal
3.
Check for any clogging in the
heat exchanger.
Error
Normal
5.
Check the circulating
fluid pressure sensor after
it is replaced.
Y
N
Error
Normal
Complete.
Replace the main board.
See section "4.5.16
Replacement of main board
& communication board".
The heat exchanger, which is
an evaporator and a part of
the refrigerant circuit, needs
to be replaced. Only a
specialized operator is
allowed to handle the
refrigerant circuit.
See document No. HRX-MM-
Q014 for replacement.
Содержание HRS012-A*-10-*
Страница 16: ...HRX MM N007 Chapter 2 Name of Parts 2 2 Component Parts HRS Series 2 4...
Страница 136: ...HRX MM N007 Chapter 3 Alarm Indication and Troubleshooting 3 3 Troubleshooting HRS Series 3 120...
Страница 200: ...HRX MM N007 Chapter 4 Service Procedure 4 5 Replacement Procedure HRS Series 4 64...
Страница 220: ...HRX MM N007 Chapter 6 Documents 6 4 Flow chart HRS Series 6 8...