No.EX
※※
-OMU1006-B
F-Slave
Failsafe slave
F_Source_Address
F-Parameter, PROFIsafe source address; address of the safe controller (Refer to also
"F-Parameter"
)
F-System
Failsafe system
A failsafe system is a system that remains in the safe state or immediately enters a safe state when specific
failures occur.
i-Parameter
Individual safety parameters of a module
Passivation
If the safety module (F-I/O device) detects an error, it switches the affected channel or all channels of the
module to the safe state. The channels are passivated. The detected errors are indicated at the safe
controller.
For a safe input module when the F-System is passivated, instead of the process values present at the safe
inputs,
“0” substitute values are provided for the safety program.
For a safe output module when the F-System is passivated, instead of the output values provided by the
safety program, “0” substitute values are transferred to the safe outputs.
PI
PROFIBUS & PROFINET International
PNO
Profibus Nutzerorganization e.V
PROFIsafe
Safety-related bus profile based on PROFIBUS DP or PROFINET. The profile defines the
communication between a safety program and the safe I/O device (F-I/O device) in a safe system
(F-System).
PROFIsafe address
Each safe module has a PROFIsafe address. Set this address on the safety module (F-I/O device) via DIP
switches and then configure it in the configuration tool for the safe controller.
PROFIsafe monitoring time
Monitoring time for safety-related communication between the safe controller (F-CPU) and safe I/O device
(F-I/O device).
This time is parameterized in the F_WD_Time F-Parameter.
Short circuit
Signal is either short circuited to another signal or 0 V.