- 27 -
No.EX
※※
-OMU1006-B
6.1.1. SF and BF indicators
Table 6-1 SF and BF indicators
SF
BF
Meaning
OFF
OFF
No fault (The SI Unit is currently exchanging data with the controller without errors)
Flash
Faulty or no connect message frame (although the SI Unit is physically connected
to an Ethernet)
●Configuration is defective, or initial commissioning has not been completed
●Device name is different from the programmed setting
●The GSD file is not correct
●The Controller is defective
---
ON
No physical connection on both PROFINET communication connector
Flashing
at 2 Hz
---
PROFIsafe communication is not established due to the following reason(s)
●No safe communication
●The SI unit is not parameterized by the Safe controller
●The parameterization is not acceptable
●The F-address is not matched
Flashing
at 0.5 Hz
---
The Safe controller requests operator acknowledgment
ON
---
The following diagnostic event(s) occurred
●Power supply is not present or is outside the permissible voltage range.
●Over voltage lockout safe state entered
●At least one valve coil has a short circuit
●Self-test has failed and a power reset is required
●The PLC mode is stop
6.1.2. L/A indicator
Table 6-2 L/A indicator
L/A
Meaning
Green ON
Connection via Ethernet to the SI Unit via BUS IN/OUT
But no transmission or reception of Ethernet telegrams on BUS IN/OUT
Orange ON
or
Flashing Green/Orange
Connection via Ethernet to the SI Unit via BUS IN/OUT
Transmission or reception of Ethernet telegrams on BUS IN/OUT
OFF
No physical connection to the port
Green Flashing
Received
“Flash Once” request