- 28 -
No.EX
※※
-OMU1006-B
6.1.3. PWR indicator
Table 6-3 PWR indicator
PWR
PWR voltage
Meaning
OFF
<16 V
PWR is not present
Green
Flashing
16 V
…19 V
PWR is below the permissible voltage range.
Green ON
19 V
…33 V
PWR is present
Red Flashing
33 V
…40 V
PWR is above the permissible voltage range.
6.1.4. PWR(V) indicator
Table 6-4 PWR(V) indicator
PWR(V)
PWR(V)
voltage
Safe power
supply status
Meaning
Yellow ON
<16 V
Not active
●PWR(V) is not present or below the permissible voltage range
●Safe power supply (safety output) for the valve is not active
Yellow Flash
16 V
…19 V
Green
Flashing
Active
●PWR(V) is below the permissible voltage range
●Safe power supply (safety output) for the valve is active
Green ON
19 V
…33 V
●PWR(V) is present
●Safe power supply (safety output) for the valve is active
Yellow/Green
Flashing
Not active
●PWR(V) is present
●Safe power supply (safety output) for the valve is not active
Red/Yellow
Flashing
33 V
…40 V
●PWR(V) is above the permissible voltage range
●Safe power supply (safety output) for the valve is not active
2020-10-30 10:03
DL085648