4. Commissioning
4.1. Configuration
4.1.1. GSD file and symbol files
In order to configure the SI Unit with your PROFIsafe controller software the appropriate GSD file is
required. The GSD file contains all of necessary information to configure the SI Unit on your PROFIsafe
controller software.
In order to represent the SI Unit in your PROFIsafe controller software the appropriate symbol files are
required.
Current GSD file and symbol files name are as follows.
GSD file: GSDML-V2.35-SMC-EX260-FPS-
.xml
Symbol file: GSDML_0083_EX260_FPS.bmp
4.1.2. Modules
EX260-FPS1 consists of the following modules.
Table 4-1 Overview of modules for EX260-FPS1
Module name
Occupied bytes
Allowable slot
Note
Inputs
Outputs
Safe valve power
4
5
1 (Fixed)
Refer to Section 4.3
,
Section
4.4
Valves (32coils)
-
4
2 (Fixed)
Refer to Section 4.5
1 Byte feedback information about
the valve output status
1
-
2 (optional)
insert to sub-slot
Refer to Section 4.6
4.2. Diagnostics parameter
The SI Unit has the following module parameters.
Table 4-2 Diagnostics parameters
Parameters
Range of values
Default
Meaning
Logic power PWR
supervision
Enable
Disable
Enable
When this parameter is enabled, the system
generates a diagnostics event if it detects that
PWR is outside the permissible voltage range.
Valve power PWR(V)
supervision
Enable
Disable
Enable
When this parameter is enabled, the system
generates a diagnostics event if it detects that
PWR(V) is outside the permissible voltage range.
WARNING:
●If safe PWR(V) monitoring is required for the application or if PWR(V) diagnostic is disabled on the
device PWR(V) failures must be managed externally by other means.
●If PWR(V) is entered lockout state, make sure valve outputs disable before PWR(V) is restarted,
otherwise valves may operate causing unintended start up.