HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 30 of 37
8
PARAMETERS SETTING
8.1
MENU ITEMS
Start the controller, then press
to enter into the parameters setting menu, see fig 1 below:
a) Set Parameters
b) Information
c) Language
8.2
PARAMETERS SETTING
When entering password interface, input password (1234) can set parts of the parameter items in
Form 8
, and input password (0318) can set all of the parameter items in
Form 8
. If there is need to set
more parameters (e.g. Voltage, Current Calibration), please contact the factory.
CAUTION:
——
Please change the controller parameters when generator is in standby mode only (e. g. Crank
disconnect conditions selection, auxiliary input, auxiliary output, various delay), otherwise,
shutdown and other abnormal conditions may happen.
——
Over voltage set value must be higher than under voltage set value, otherwise over voltage and
under voltage condition may occur simultaneously.
——
Over speed set value must be higher than under speed set value, otherwise over speed and
under speed condition may occur simultaneously.
——
Please set the generator frequency value as low as possible when cranking, in order to make the
starter be separated quickly as soon as possible.
——
Auxiliary input 1~5 could not be set as same items; otherwise, there are abnormal functions.
However, the auxiliary output 1~4 can be set as same items.
——
If need to shut down after cooling, please set any digital input as “WTH STOP by cool”, then
connect this input port to ground soundly.
8.3
INFORMATION
LCD will display software version, issue date of the controller.
Note: In this interface, press
will display the auxiliary inputs and outputs status.
8.4
LANGUAGE
Chinese and English interface can be selected.
8.5
LCD CONTRAST REGULATION
Simultaneously press
and
or
can adjust contrast in order to make LCD more
distinct. The range of regulation is 0-7.
Note: In setting process, press
in any time will break the parameter setting off and return
back to main interface.