HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 24 of 37
No
Items
Range
Default
Description
62
Inhibit WTH
(0-1)
0
Factory default: High Temp. Shutdown.
When
high
temperature
occurs,
shutdown alarm is active. Table8 Note1
63
Inhibit OPL
(0-1)
0
Factory default: when low oil pressure
occurs, shutdown alarm is active.
Table8 Note2
64
AC System
(0-3)
0
0: 3P4W; 1: 2P3W
2: 1P2W; 3: 3P3W
65
Engine Temp
Curve
(0-9)
8
SGX
66
Oil Pressure
Curve
(0-9)
8
SGX
67
Fuel Level Curve
(0-5)
3
SGD
68
Generator Poles
(2-64)
4
The gain is regulated during the genset
is idle running.
69
Temp.S Open
Action
(0-2)
1
0 Indicate; 1 Warn; 2 Shutdown
70
OP.S Open Action (0-2)
1
0 Indicate; 1 Warn; 2 Shutdown
71
Maintenance Time (0-5000)h
30
Used to set the intermission of
maintenance time.
72
Maintenance
Action
(0-2)
0
0 Negative; 1 Warn; 2 Shutdown
When maintenance action is set to
Negative, the alarm will reset.
73
Aux.Sensor1 Type (0-3)
0
0 Not used; 1 Temp sensor
2 Pressure sensor; 3 Level sensor
74
Aux.Sensor1
Curve
(0-9)
0
75
Aux.S.1 H Warn
(0-1000)
0
When the value of external aux. sensor
has exceeded this value, it will initiate
warn alarm.
76
Aux.S.1 H
Shutdown
(0-1000)
0
When the value of external aux. sensor
has exceeded this value, it will initiate
shutdown alarm.
77
Aux.S.1 L Warn
(0-1000)
0
When the value of external aux. sensor
has fallen below this value, it will initiate
warn alarm.
78
Aux.S.1 L
Shutdown
(0-1000)
0
When the value of external aux. sensor
has fallen below this value, it will initiate
shutdown alarm.
79
Crank Angle
(0-100)%
45
The throttle opening before the genset
is starting.
80
Crank Disc. Angle
(0-100)%
35
The initial opening of the throttle after
the genset is started.