HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 15 of 37
5.2
SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and shuts down
generator. Besides, the alarm information will be displayed on the LCD.
Table 6- Shutdown alarms as following
No.
Type
Description
1
Emergency
Stop
When the controller detects that there is Emergency Stop input, it will
initiate a shutdown alarm and the alarm information will be displayed on
the LCD.
2
High
Temperature
When the controller detects that there is High Temperature input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
3
Low Oil
Pressure
When the controller detects that there is Low Oil Pressure input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
4
Over Speed
When the controller detects that the generator speed has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
5
Under Speed
When the controller detects that the generator speed has fallen below
the pre-set value, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
6
Loss of Speed
Signal
When the controller detects the speed is 0 and the Loss of Speed Signal
delay is NOT set as 0, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
7
Gen Over Volt.
When the controller detects that the generator voltage has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
8
Gen Under
Volt.
When the controller detects that the generator voltage has fallen below
the pre-set value, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
9
Gen Over
Current
When the controller detects that the generator current has exceeded the
pre-set value and the Overcurrent Stop Threshold delay is NOT set as 0,
it will initiate a shutdown alarm and the alarm information will be
displayed on the LCD.
10
Fail To Start
If the engine does not fire after the pre-set number of attempts, it will
initiate a shutdown alarm and the alarm information will be displayed on
the LCD.
11
Gen Over Freq.
When the controller detects that the generator frequency has exceeded
the pre-set value, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
12
Gen Under
Freq.
When the controller detects that the generator frequency has fallen
below the pre-set value, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
13
No gens freq
When the controller detects the generator frequency is 0, it will initiate a
shutdown alarm and the alarm information will be displayed on the LCD.