HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 23 of 37
No
Items
Range
Default
Description
35
Fuel Pump Off
(0-100)%
80
When fuel level is higher than the
pre-set value and last for 10s, it will
initiate a fuel pump off signal.
36
Digit Output1
(0-17)
2
Factory default: Energized To Stop
37
Digit Output2
(0-17)
3
Factory default: Idle Control
38
Digit Output3
(0-17)
5
Factory default: Close Generator
39
Digit Output4
(0-17)
7
Factory default: Open Generator
40
Digit Input1 Set
(0-16)
1
Factory default: High Temperature Input
41
Digit Input1 Act
(0-1)
0
Factory default: Close to active
42
Digit Input1 Delay
(0-20.0)s
2.0
43
Digit Input2 Set
(0-16)
2
Factory default: Low Oil Pressure Input
44
Digit Input2 Act
(0-1)
0
Factory default: Close to active
45
Digit Input2 Delay
(0-20.0)s
2.0
46
Digit Input3 Set
(0-16)
10
Factory default: Remote Start
47
Digit Input3 Act
(0-1)
0
Factory default: Close to active
48
Digit Input3 Delay
(0-20.0)s
2.0
49
Digit Input4 Set
(0-16)
11
Factory default: Fuel Level Warn
50
Digit Input4 Act
(0-1)
0
Factory default: Close to active
51
Digit Input4 Delay
(0-20.0)s
2.0
52
Digit Input5 Set
(0-16)
12
Factory default: Cooling Liquid Level
Warn
53
Digit Input5 Act
(0-1)
0
Factory default: Close to active
54
Digit Input5 Delay
(0-20.0)s
2.0
55
Power On Mode
(0-2)
0
0: Stop Mode
1: Manual Mode
2: Auto Mode
56
Slave Address
(1-254)
1
Communication address of controller.
57
Passwords
(0-9999)
1234
58
Disc. Condition
(0-5)
2
There are 2 conditions of disconnecting
starter
with
engine:
Generating,
Magnetic Sensor and Oil Pressure.
Each condition can be used alone and
simultaneously to separating the start
motor and genset as soon as possible.
59
Disconnect Speed (0-3000) r/min
360
When the engine speed has exceeded
the
set
value,
starter
will
be
disconnected.
60
Disconnect Freq
(10.0-30.0)Hz
14.0
When the generator frequency has
exceeded the set value, starter will be
disconnected.
61
Disconnect OP
(0-400)kPa
200