HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 28 of 37
Table 11-
SENSOR SELECTION
No
Items
Description
Note
1
Temp Sensor
0 None
1Defined Resistance
2 VDO
3 SGH
4 SGD
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
9 Reserved
The range of Defined Resistance is:
0-
6000Ω, factory default is SGX.
2
Pressure Sensor
0 None
1Defined Resistance
2 VDO 10bar
3 SGH
4 SGD
5 CURTIS
6 DATCON 10bar
7 VOLVO-EC
8 SGX
9 Reserved
The range of Defined Resistance is:
0-
6000Ω, factory default is SGX.
3
Fuel Level Sensor
0 None
1Defined Resistance
2 SGH
3 SGD
4 Reserved
5 Reserved
The range of Defined Resistance is:
0-
6000Ω, factory default is SGX.
Table 12-
Conditions of crank dinsconnect selection
No.
Setting Description
0
Speed sensor
1
Gen frequency
2
Speed Gen frequency
3
Speed Oil Pressure
4
Gen fre Oil Pressure
5
Speed Gen fre Oil Pressure
NOTE:
a) There are 3 conditions to make starter disconnected with engine, that is, speed sensor, generator
frequency and oil pressure. Speed sensor and generator frequency can be used separately, oil
pressure needs speed sensor and generator frequency simultaneously for cooperation in order to
make the starter motor is separated with engine immediately and can check crank disconnect
exactly.