Table 9- Enable definition of programmable output ports
No
Items
Description
0
Not Used
Output port is d
eactivated when “Not Used” is selected.
1
Common Alarm
Include all shutdown alarms and warning alarms. When there is
warning alarm only, it is not self-lock; when a shutdown alarm
occurs, it is self-lock until the alarm is reset.
2
Energized to Stop
Sui
table for genset with electromagnet and will active after “stop
idle delay”. It is deactivated when the “ETS Solenoid delay”
expires.
3
Idle Control
Used for engine which has idles. Close before starting and open
in warming up delay; Close during stop idle delay and open
when stop is completed.
4
Preheat Control
Close before starting and open before power up;
5
Close Generator
When close time is 0, it‟s continuous output.
6
Reserved
7
Open ATS
When close time is 0, it‟s disabled.
8
Raise Speed
Close when the generator enters into Warming Up delay (close
time: warming up delay) while open when Aux. Raise Speed
input is active.
9
Drop Speed
Close when the generator enters into Stop Idle delay/ Energized
to Stop delay (close time: Stop Idle delay) while open when Aux.
Drop Speed input is active.
10
Generator Run
Action when genset is normal running while deactivated when
engine speed is lower than the “crank disconnect speed”.
11
Fuel Pump Control
Close when fuel level is lower than the “Fuel Pump On” value or
when low fuel level warning input is active; Open when fuel level
is higher than the “Fuel Pump Off” and low fuel level warning
input is deactivated;
12
High Speed Control
Close when the generator enters into Warming Up delay while
open after cooling delay.
13
In Auto Mode
The controller is in automatic mode.
14
Reserved
15
Reserved
16
Reserved
17
Reserved