HGMS61 Genset Controller User Manual Page 21 of 47
No.
Items
Range
Default
Description
2
Stop Delay
(0~3600)s
1
Time from mains normal or remote start
signal is inactive to genset stop.
3
Start Times
(1~10) times
3
When engine start failure, it’s the maximum
cranking times. When setting crank times
out, controller will send start fail signal.
4
Preheat Delay
(0~300)s
0
Time of pre-powering heat plug before
starter is powered up.
5
Cranking Time
(3~60)s
8
Time of starter power up each time.
6
Crank Rest Time
(3~60)s
10
The second waiting time before power up
when engine start fails.
7
Safety On Time
(1~60)s
10
Alarm for low oil pressure, high temp, under
speed, under frequency /voltage, Failed To
Charge are all inactive.
8
Start Idle Time
(0~3600)s
0
Idle running time of genset when starting.
9
Warming Up Time
(0~3600)s
10
Warming time between genset switch on
and high speed running.
10
Cooling Time
(3~3600)s
10
Time for cooling before genset taking of
load.
11
Stop Idle Time
(0~3600)s
0
Idle running time when genset stop.
12
ETS Solenoid Hold
(0~120)s
0
Stop electromagnet’s power on time when
genset is stopping.
13
Fail to Stop Delay
(0~120)s
20
If “ETS Solenoid Hold” set as 0, it is the time
from end of idle delay to genset at rest; if
not 0, it is from end of ETS solenoid delay to
genset at rest.
14
Switch Close Delay
(0.0~10.0)s
5.0
Mains’ or generator’s switch closing pulse
width, when it is 0, output is continuous.
15
Flywheel Teeth
(10.0~300.0)
118
Number of flywheel teeth, it can detect
disconnection conditions and engine speed.
16
Gen Abnormal Delay
(0~20.0)s
10.0 Over or under volt alarm delay
17
Gen Over Voltage
Shutdown
(30~60000)V
264
When genset voltage is over the value and
keeps the set “Gen Abnormal Delay”,
generator over voltage is active and it will
send generator abnormal stop alarm. When
set as 60000V, the over voltage signal is not
detected.
18
Gen Under Voltage
Shutdown
(30~60000)V
196
When sampling voltage is under the value
and keeps the set “Gen Abnormal Delay”,
generator under voltage is active and it send
generator abnormal stop alarm. When set as
30V, the under voltage signal is not
detected.