HGMS61 Genset Controller User Manual Page 34 of 47
—
Emergence stop input must be connected to positive of starting battery via normally close contact
of emergency stop.
—
Take proper actions to prevent engine to disconnect crank (e. g. Remove the connections of fuel
value). If checking is OK, connect start battery, select Manual Mode, controller will execute the
program.
—
Set controller as Manual Mode, press “start” button to start genset. If failed within the setting
crank times, controller will send “Failed to Start” signal; then press “stop” to reset controller.
—
Recover actions of preventing engine to disconnect crank (e. g. Connect wire of fuel value), press
“start” button again, genset will start. If everything goes well, genset will normally run after idle
running (if configured). During this period, watch for engine’s running situations and voltage and
frequency of alternator. If there is abnormal, stop genset and check all connections according to
this manual.
—
Select the Auto Mode from front panel. After remote start signal is active, genset will start
automatically and run in normal status, and then send gen close order to make geset take load.
—
If there are any other questions, please contact SmartGen’s service.