HGMS61 Genset Controller User Manual Page 32 of 47
8
PARAMETER SETTING
After controller powered on, press
to enter into the parameters setting menu:
1)
Parameters Setting
2)
Controller Information
3)
Language
4)
Event Log
5)
Maintenance Setting
—
Parameters Setting
“0318” can set all items in Table 11 during inputting password. When default password has been
changed, it needs to input the same password with controller for parameter setting via PC software.
If more parameter items need to be set or password is forgotten, such as voltage and current
calibration, please contact with the factory.
Notes:
1)
Please modify the parameters in standby mode (crank conditions, programmable input and output
configuration, multi delays, etc.) otherwise shutdown alarm or other abnormal conditions may
appear.
2)
The over voltage threshold must be greater than the under voltage threshold; otherwise over
voltage and under voltage will occur at the same time.
3)
The over speed threshold must be greater than under speed threshold, otherwise over speed and
under speed will occur at the same time.
4)
Set frequency value (after crank disconnect) as low as possible, in order to disconnect starter
quickly.
5)
Programmable input 1-4 cannot be set as the same items, otherwise it cannot realize correct
function; programmable output 1-4 can be set as the same item.
6)
If need to shut down after cooling, please set any input as “stop after cooling “, then connect this
input to ground; or set high temperature stop action as “cooling stop”
—
Controller Information
1)
LCD will display some information of controller, such as software version, issue date.
Note:
Pressing
will display the status of digital inputs and outputs.
2)
Language Slection
User may select display language as Chinese, English, Spanish, Russian, Portuguese, Turkey,
Polish and French.
3)
LCD contrast ratio adjustment
Press
and
(or
and
) and adjust LCD contrast ratio, which shall make the LCD
characters clearer. Adjustment range is 0-9.