HGMS61 Genset Controller User Manual Page 17 of 47
6
CONNECTIONS
6.1
HGMS61M CONTROLLER PANEL
Fig.2 – HGMS61M Controller Panel Drawing
Table 9– HGMS61M Terminal Connection Description
No.
Function
Cable
Size
Description
Main Terminals
1
Aux. Relay Output 3
1.5mm
2
Relay normally open, rated 16A, volt-free contact
output.
2
3
Aux. Relay Output 4
1.5mm
2
Relay normally open, rated 16A, volt-free contact
output.
4
5
Aux. Relay Output 1
1.5mm
2
B+ is supplied by 21 points, rated 7A.
6
Aux. Relay Input 1
1.0mm
2
Ground connection is active (B-).
7
Aux. Relay Input 2
1.0mm
2
Ground connection is active (B-).
8
Aux. Relay Input 3
1.0mm
2
Ground connection is active (B-).
9
Aux. Relay Input 4
1.0mm
2
Ground connection is active (B-).
10 Temp. Sensor Input
Connect to temperature sensor.
11
Oil Pressure Sensor
Input
Connect to pressure sensor.
12 Level Sensor Input
Connect to level sensor.
13 Sensor Common
1.0mm
2
Controller inside has been connected to B-.
14
Charging Generator D+
Input
1.0mm
2
Connect to D+ (WL) terminal. If without, the terminal
is not connected.
15
Speed Sensor Input
Or ECU CAN Input
0.5mm
2
HGMS61MCAN:
connect
to
ECU
CANBUS,
impedance-120Ω shielding wire is recommended, its
single-end connect with ground.
HGMS61M: connect to speed sensor, shielding wire
16
0.5mm
2