HGMS61 Genset Controller User Manual Page 18 of 47
No.
Function
Cable
Size
Description
is recommended. No.16 controller inside has been
connected to B-.
17 RS485-
0.5mm
2
Impedance-120Ω shielding wire is recommended, its
single-end connect with ground.
18 RS485+
0.5mm
2
19 Fuel Relay Output
1.5mm
2
B+ is supplied by 21 points, rated 10A.
Relay specification: DC 24V.
20 Start Relay Output
1.5mm
2
21 DC input B+
2.5mm
2
Connect to start battery positive post, 32A fuse is
used in controller.
22 DC input B-
2.5mm
2
Connect to battery negative post.
23 ACT1
2.5mm
2
Connect to external executor. The terminal in
controller is connected to Terminal 10 of Connector
B.
24 ACT2
2.5mm
2
Connect to external executor. The terminal in
controller is connected to Terminal 7 of Connector B.
25 CB+
2.5mm
2
Connect to external start battery positive post. The
terminal in controller is connected to Terminal 1 of
Connector B.
26 CB-
2.5mm
2
Connect to external start battery negative post. The
terminal in controller is connected to Terminal 2 of
Connector B.
27
CT A Phase Monitoring
Input
1.5mm
2
Externally connect to CT secondary coil. (Rated
5A)
28
CT B Phase Monitoring
Input
1.5mm
2
Externally connect to CT secondary coil. (Rated
5A)
29
CT C Phase Monitoring
Input
1.5mm
2
Externally connect to CT secondary coil. (Rated
5A)
30 CT Sensor Common
1.5mm
2
Refer to installation instructions.
31 UOUTPUT
1.0mm
2
Generator U-phase monitoring input will output after
the fuse.
32
Generator
U-phase
Voltage
Monitoring
Input
1.0mm
2
Connect to genset output U-phase, the control uses
10A fuse.
33
Generator
V-phase
Voltage
Monitoring
Input
1.0mm
2
Connect to genset output V-phase, the control uses
10A fuse.
34
Generator
W-phase
Voltage
Monitoring
Input
1.0mm
2
Connect to genset output W-phase, the control uses
10A fuse.
35 Genset N1 Wire Input
1.0mm
2
Connect to genset output N wire.
36
Mains R-phase Voltage
Monitoring Input
1.0mm
2
Connect to Mians R-phase, the controller uses 10A
fuse.
37 Mains N Wire Input
1.0mm
2
Connect to Mains N wire.
Connector A ( Connect to HGMS61D)
1
B+ IN
2.5mm
2
Connect Terminal 6 (B+ OUT) to this terminal
through a power switch to supply for positive post of
HGMS61M.
2
B+ OUT1
1.5mm
2
Supply power to positive post of HGMS61D.
3
B-
2.5mm
2
Negative post of controller power.