HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
24
of
68
6.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and shuts down
generator.
Shutdown alarms as following:
No.
Type
Description
1
Emergency Stop
When the controller detects an emergency stop alarm signal,
it will initiate a shutdown alarm.
2
Over Speed
When the controller detects that the generator speed has
exceeded the pre-set value, it will initiate a shutdown alarm.
3
Under Speed
When the controller detects that the generator speed has
fallen below the pre-set value, it will initiate a shutdown alarm.
4
Loss of Speed Signal
When the controller detects that the generator speed is 0 and
the action select “Shutdown”, it will initiate a shutdown alarm.
5
Fail To Start
If the engine does not fire after the pre-set number of
attempts, it will initiate a shutdown alarm.
6
Gen Over Current
When the controller detects that the genset current has
exceeded the pre-
set value and the action select “Shutdown”,
it will initiate a shutdown alarm.
7
Maintenance Due
When count down time is 0 and the action select “Shutdown”,
it will initiate a shutdown alarm.
8
ECU Shutdown
If an error message is received from ECU via J1939, it will
initiate a shutdown alarm.
9
ECU Com Fail
If an error message is
NOT
received from ECU via J1939, it
will initiate a shutdown alarm.
10
Aux High Temp
The controller will initiate a shutdown alarm if the input is
active.
11
Aux Low OP
The controller will initiate a shutdown alarm if the input is
active.
12
Temperature Sensor
Open Circuit
When the controller detects that the temperature sensor is
open circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
13
High Temperature
When the controller detects that engine temperature has
exceeded the pre-set value, it will initiate a shutdown alarm.
14
Oil Pressure Open
Circuit
When the controller detects that the oil pressure sensor is
open circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
15
Low Oil Pressure
When the controller detects that the oil pressure has fallen
below the pre-set value, it will initiate a shutdown alarm.