![Smartgen HGM7110DC Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/smartgen/hgm7110dc/hgm7110dc_user-manual_1297522029.webp)
HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
29
of
68
NO.
Functions
Cable
Size
Remark
14
Normally
open
outputs, rated 7A
15
Aux. Output 3
2.5mm
2
Normally
open
outputs;
volts
free;
rated 16A
16
17
Aux. Output 4
2.5mm
2
18
19
NC
Reserved
20
B(+)
1.5mm
2
Connect to GOV or AVR.
21
A(-)
1.5mm
2
22
User
Config.
Current
IDC 1+
1.0mm
2
Connect
to
(4-20)mA
or
(0-5)V
current
transformer.
23
IDC 1-
1.0mm
2
24
User
Config.
Current
IDC 2+
1.0mm
2
Connect
to
(4-20)mA
or
(0-5)V
current
transformer.
25
IDC 2-
1.0mm
26
A1+
1.0mm
2
1# Accumulator Voltage Input: (0~75V)
。
27
A1-
1.0mm
28
B1+
1.0mm
2
If “Acc priority” or “Gen priority” is selected,
generator voltage will be input; If “Two accs” is
selected, generator voltage or 2# accumulator
voltage (0-75V) will be input (depends on
generator voltage status).
29
B1-
1.0mm
2
30
MP1
Connected
with
Speed
sensor,
shielding
line
is
recommended.
31
MP2,
(-Ve)
has
already
connected
internal
32
Aux. Input 1
1.0mm
2
Ground connected is
active (-Ve)
Details see form 3
33
Aux. Input 2
1.0mm
2
Ground connected is
active (-Ve)
34
Aux. Input 3
1.0mm
2
Ground connected is
active (-Ve)
35
Aux. Input 4
1.0mm
2
Ground connected is
active (-Ve)
36
Aux. Input 5
1.0mm
2
Ground connected is
active (-Ve)
37
Aux. Input 6
1.0mm
2
Ground connected is
active (-Ve)
38
Aux. Input 7
1.0mm
2
Ground connected is
active (-Ve)