HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
37
of
68
No.
Items
Parameters
Defaults
Description
26
Current
2
Curve Type
(0-1)
0
0: 4-20mA
1: 0-5V
27~
42
Current
2
Curve
Contents
X(0-32762)mA/V 0
Custom (x0,y0),(x1,y1)
Y(0-32767)A
0
Switch Setting
1
Close Time
(0-20.0)s
5.0
2
Open Time
(0-20.0)s
3.0
3
Check Time
(0-20.0)s
5.0
4
Open
Check
Enable
(0-1)
0
0: Disable ;1: Enable
5
Check
Fail
Warn
(0-1)
0
0: Disable ;1: Enable
Module Setting
1
Power
On
Mode
(0-2)
0
0: Stop mode 1: Manual mode
2: Auto mode
2
Module
Address
(1-254)
1
Controller’s address during remote
sensing.
3
Stop Bits
(0-1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0-2)
0
0: Simplified Chinese 1: English
2: Others
5
Password
(0-65535)
00318
For entering advanced parameters
setting.
GSM Setting
1
GSM Enable
(0-1)
0
0: Disable; 1: Enable
2
Phone
Number
Max.20 digits
Its national and area’s cods must be
added. e.g. China: 8613666666666.
Scheduling And Maintenance Setting
1
Scheduled
Run
(0-1)
0
0: Disable; 1: Enable
2
Scheduled Not
Run
(0-1)
0
0: Disable; 1: Enable
3
Maintenance
(0-1)
0
0: Disable; 1: Enable
Analog Sensors Setting
Temperature Sensor
1
Curve Type
(0-15)
7
SGX See form 5.