HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
33
of
68
No.
Items
Parameters
Defaults
Description
Mode”. If the genset enters into the
“Constant
Voltage
mode”,
the
accumulator charges the genset with
its set value as soon as the charge
current has fallen below the set value.
The charging is finished if the charging
voltage has reached the “Charge Stop
Voltage”.
21 Float Voltage
(0-1000) %
80
Reserved
22
Nominal
Voltage
(0-1000) %
100
It’s the load voltage if the “Gen
Priority” is selected.
23 Charge OC
(0-1)
0
0: Disable; 1: Enable
(0-200)%
120
Charging Over Current Percentage
(0-3)
0
0: Warn; 1: Shutdown;
2: Trip and Stop; 3: Trip
(0-3600)s
10
Charging Over Current Delay
24
Charge
increment
(0-10) A
1
Adjust the charge increment manually
in Manual mode.
25
Charge
Rest
Time
(0-1)
0
0: Enable; 1: Disable
(0-300)h
30
In Auto mode, it is the waiting time
before second charging.
26
Charge
Limit
Time
(0-1)
0
0: Enable; 1: Disable
(0-3)
0
0: Warn; 1: Shutdown;
2: Trip and Stop; 3: Trip
(0-300)h
1
After the module is start successfully,
if the charging is not finished after the
set delay has expired, “Charge Limit
Time” alarm will be initiatd.
27 System Mode
(0-2)
0
0: Accumulator Priority
1: Gen Priority
2: Double Accumulator Priority
28
Two
Accumulators
Transfer Mode
(0-1)
0
0: Gap Power Supply
1:Uninterrupted Power Supply
29 Control Mode
(0-2)
0
0:GOV;
1:PWM;
2:AVR
30 GOV Volt. Min. (0-10.0)V
0
GOV output minimum voltage