HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
28
of
68
7 WIRING CONNECTION
HGM7110DC
controller’s rear as following:
Description of terminal connection:
NO.
Functions
Cable
Size
Remark
1
DC Input -Ve
2.5mm
2
Connected with negative of starter battery.
2
DC Input +Ve
2.5mm
2
Connected with positive of starter battery. If wire
length is over 30m, better to double wires in
parallel. Max. 20A fuse is recommended.
3
Emergency Stop
2.5mm
2
Connected with +Ve via emergency stop button.
4
Fuel (16A)
1.5mm
2
+Ve is supplied by terminal 3, rated 16A
5
Crank (16A)
1.5mm
2
+Ve is supplied by
terminal 3, rated 16A
Connected to starter coil
6
Aux. Output 1
1.5mm
2
+Ve is supplied by
terminal 2, rated 7A
Details see form 2
7
Aux. Output 5
1.5mm
2
8
Aux. Output 6
1.5mm
2
9
GND
1.5mm
2
Connect to PWM.
10
PWMOUT
1.5mm
2
11
Charger (D+)
1.0mm
2
Connected with charger’s D+ (WL) terminals. Be
hanging in the air If there is no this terminal.
12
Aux. Output 2
1.5mm
2
Normally
close
outputs, rated 7A
Details see form 2
13
Public points of relay