![Smartgen HGM7110DC Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/smartgen/hgm7110dc/hgm7110dc_user-manual_1297522063.webp)
HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
63
of
68
14.7 DEUTZ EMR2
Terminals of controller
F connector
Remark
Fuel relay output
Expand 30A relay; battery
voltage of terminal 14 is
supplied by relay. Fuse is
16A.
Start relay output
-
Connect to starter coil directly
-
1
Connect to battery negative pole
CAN GND
-
CAN
communication
shielding
line(connect
with
controller’s
terminal only)
CAN(H)
12
Impedance 120Ω connecting line is
recommended.
CAN(L)
13
Impedance 120Ω connecting line is
recommended.
Engine type: VolvoEDC4
14.8 JOHN DEERE
Terminals of controller
21 pins connector
Remark
Fuel relay output
G,J
Start relay output
D
CAN GND
-
CAN communication shielding
line(connect
with
controller’s
terminal only)
CAN(H)
V
Impedance 120Ω connecting line
is recommended.
CAN(L)
U
Impedance 120Ω connecting line
is recommended.
Engine type: John Deere