EM100 Mini Inverter
33
VS
VS Analog
voltage input
0/2
~
10V, input impedance: 1M
Ω
Max. input voltage:15V
GND
Common port
Input/output signal common port
IS
IS Analog
current /voltage
input
IS can be configurated as current
input or voltage input and switched
by S2. Input range:0/4
~
20mA or
0/2
~
10V
Analog Output
M0
Analog output
terminal M0
0~10V, output accuracy: ±2%,
Max. output current: 2mA,
Impedance allowed: >10k
Ω
Multi-function
Numeric Output
Y1
OC output
terminal
Programmable multi-function output
terminals as shown in F03.00
Communication
A+
RS485
Communication
interface terminal
RS485 A+
A- RS485
A-
Numeric Input
X1
Multi-function
input terminal
Program the relevant terminals by
setting F02
.
00
~
F02
.
05 to achieve
the input control of setting function
X2
X3
X4
X5
X6
GND
Common port
Common port for input/output signal
SPI
Communication
RJ45
External keypad
terminal
For connecting external operator
Relay Output
EA
Relay output
terminal
EA-EC: NO
EB-EC: NC
EB
EC
Jumper Switch
S1
Selecting resistor
applicable to
RS485 terminal
Jumper switch for selecting resistor
which is applicable to RS485
terminal
OFF: No terminal resistor
ON: With terminal resistor
Default is no terminal resistor
S2
IS
Voltage/Current
Input Option
Jumper switch for setting IS as
voltage input or current input
OFF:Current input
ON: Voltage input
Default is set as current input.