User Manual
EM100 Mini Inverter
83
No.
Function
Range
Unit
Default
Type
F06.10
Dynamic Brake
Control
0: Disabled
1: Enabled
2: Enabled at running
3: Enabled at deceleration
1
〇
F06.11
Dynamic Brake
Voltage
380V:510
~
800
220V:300
~
400
V
700
〇
380
F06.12
Brake Duty
Ratio
5.0
~
100.00
% 100.00
〇
F06.10
sets the enabling range of dynamic brake. When F06.10=0, dynamic brake is
disabled. If F06.11
≠
0, dynamic brake enabled when meeting the setting value of F06.11.
F06.11
sets the voltage point of dynamic brake. If the present status meets the setting range
of F06.10, DC bus voltage > setting voltage of F06.11, then dynamic brake is enabled.
380V: Inverter rated voltage is 380V. 220V: Inverter rated voltage is 220V.
F06.12
sets the duty ratio of voltage brake when dynamic brake is enabled.
No.
Function
Range
Unit
Default Type
F06.13
Fan Control
0: Run at power-on
1: Smart mode
1
〇
After power is on, the fan runs per the control mode after running for 2 minutes regardless
of the working status of inverter.
F06.13=0
The fan runs directly after inverter is power-on.
F06.13=1
Smart mode: Fan runs if the temperature of heatsink >45
℃
. If the temperature of
heatsink <35
℃
, fan stops. When the temperature of heatsink is between 35
℃
~45
℃
, fan
remains its previous status.
No.
Function
Range
Unit
Default Type
F06.15
JOG Key Function
Setting
0: Disabled
1: Jog running function
2: F/R switching function
1
〇
F06.15=0
key is disabled.
F06.15=1
key is for jog running.
F06.15=2
key is for
switching forward and reverse.
No.
Function
Range
Unit
Default Type
F06.16
Function of STOP
Key
0: Enabled in keypad
start/stop mode
1:Enabled in all
start/stop modes
2: Enabled in keypad
start/stop mode, external
fault trips in other
start/stop modes
0
〇
F06.16=0
Enabled in keypad start/stop mode1, and disabled in other start/stop modes.
F06.16=1
Enabled in all start/stop modes.