F07.08
Overvoltage Stall
Mode 2 Integral Time
0.00
~
300.00
0.00: Integration Disabled
S
10.00
●
F07.09
Overheating Prealarm
Temperature
50~115
℃
85
〇
F07.10
Motor Overload
Protection Options
0: Prohibited
1: Permitted
1
〇
F07.11
Motor Overload
Protection Time
30
~
300 S
60
〇
F07.12
Fault Retry Control
Ones place: Fault retry times
0: Fault retry prohibited
1~3: Fault retry for 1, 2, and 3
times
4: Unlimited fault retry
Tens place:
In the process of fault retry,
fault output terminals:
0
:
Off 1
:
On
00
〇
F07.13
Fault Retry Timelag
0.01
~
30.00 S
0.50
〇
F07.14 Timelag
without
Fault
0.01
~
30.00 S
10.00
〇
F07.15
Fault Retry Options
OL ILP SLU
SOU
SOC
11111
〇
1 1 1 1 1
0: Fault retry permitted
1: Fault retry prohibited
SOC is LSB, arrange in logical
order, the 6
th
~the 8
th
bits are
not used
F07.16 Not
Used
F07.17 Disabled
Trips
5
~
8 Bits
0000
0000
〇
* EEd EHt OL
0 0 0 0
1
~
4 Bits
tbr OLP ILP SLU
0 0 0 0
0
:
Enabled
,
1: Disabled
SLU is LSB, arrange in logical
order, the 8
th
bit is not used
F08 Group: Preset Speed and PLC Parameters
F08.00 Preset Speed 1
0.00
~
Fmax Hz
0.00
●