User Manual
EM100 Mini Inverter
78
No.
Function
Range
Unit
Default
Type
F04.02
Acceleration/
Deceleration Mode
0:Linear mode
1:S curve mode
0
〇
F04.03
S Curve Time
0.00
~
600.00
S 0.00
〇
F04.04
Not Used
-
-
Linear Acceleration/Deceleration
F04.02=0 Acceleration/Deceleration is in linear mode.
S Curve Acceleration/Deceleration
F04.02=1 Acceleration/Deceleration is in S curve mode. The 1
st
section and the last section
in accelerating or decelerating are in smooth transition. The acceleration/deceleration curve
is similar to S curve. When it is in S curve, the final acceleration/deceleration time= S
curve time+ Linear acceleration/deceleration time. See Figure 6-13 for 2
acceleration/deceleration modes.
Figure6-13 Linear and S Curve Acceleration/Deceleration
No.
Function
Range
Unit
Default
Type
F04.05
Stop Mode Options
0: Ramp-to-stop
1: Coast-to-stop
0
〇
Ramp-to-stop
Set F04.05=0,
motor ramps to stop as per setting deceleration time
【
(Default is as per
F00.10 deceleration 1)
】
Coast-to-stop
Set F04.05=1,
inverter will block PWM output while inputting stop command, motor will
coast to stop. Stop time is up to the motor and the load inertia. If a coast-to-stop terminal is
set and when it is on, the inverter will enter coast-to-stop status immediately, and it will not
run again if the terminal is off. It is required to input the run command again to restart
inverter.