F00.07 (primary numeric frequency) which will assist user to edit setting frequency. If
there is no operation with keypad for 5 seconds, keypad display will return the sub-menu
of monitoring code group.
Edit setting frequency by press
or
in operation status or stop status.
4.2.7 Fault Reset/Monitoring
Select a code from E00.00~E00.05 to view its parameter value on sub-menu of fault
monitoring. For instance, see Figure 4-7 for the procedures to view E00.02 parameter.
Referring to Figure 4-7, press
or
in fault monitoring status to view each fault
status, and switch to fault code to view the last 3 faults status by pressing
.
After clearing fault, press
to reset parameter setting status from fault status.
Figure 4-7 Procedures of Viewing Fault Monitoring Parameters
4.2.8 Function of JOG Key
When F06.15=1, inverter runs as per setting jog frequency when pressing
, and will
stop immediately when releasing
.
When F06.15=2, inverter will switch running direction forward with reverse once when
pressing
. F/R indicator on the keypad: OFF refers to forward, ON refers to reverse.
4.2.9 Start/Stop
If F00.02 ones place=0, start/stop of inverter is in keypad control mode. Inverter starts
when pressing
. In operation status, inverter will stop immediately when pressing
.
4.2.10 Insufficient Operation Conditions
When soft-start relay is off and pressing
or
(when
function is jog
running), the keypad displays P.OFF for 1 second, and inverter does not run and output.
After the operation conditions can meet requirements, inverter will run when giving
operation command again.
4.2.11 Autotuning Motor Parameter via Keypad Operation
After setting F01.13=1(Stationary Autotuning) or F01.13=2(Rotational Autotuning),
press
and confirm, keypad displays rUN, then press
to start autotuning
motor parameters. Keypad displays StUdy in the process of autotuning, F01.13=0 after
autotuning finished.