46
The SafeLINC FPII web pages allow you to view general and specific system data. This section
describes how to bring up summary data for the host panel, as well as individual cards and points.
To view TrueAlarm Service reports, select Service under TrueAlarm Reports in the Logs and
Reports section at the top of the screen. TrueAlarm Service reports display the device number and
custom label for each point in a channel, as well as:
Alarm At.
The percentage of a value/ number of units of a value (for example, smoke on a smoke
detector) that the device needs to sense to go into alarm.
Average Value.
The number of units of a value (for example, smoke on a smoke detector) that the
device currently detects on average.
Current/% Alarm.
The current number of units of a value/ percentage of a value (for example,
smoke on a smoke detector) that the device currently senses.
Peak/% Alarm.
The highest number of units of a value/ percentage of a value (for example,
smoke on a smoke detector) that the device has sensed.
Current State.
Shows the message the device is sending to the panel (Normal, Alarm, Trouble,
Supervisory, No Response, etc.).
Email This Report.
Allows you to email the displayed report. The size of the report may require
the system to send multiple email messages. When the report is requested, it will be sent via email
to the user who is currently logged into the system.
To view TrueAlarm Status reports, select Status under TrueAlarm Reports in the Logs and Reports
section at the top of the screen. TrueAlarm Status reports display the zone name and custom label
for each point in a channel, as well as:
Current Sensitivity.
The percentage of a value (for example, smoke on a smoke detector) that
must be detected by the device to go into alarm.
Device Status.
Shows the message the device is sending to the panel (Normal, Alarm, Trouble,
Supervisory, No Response, etc.).
Almost Dirty.
Displays *
YES
* when the average device sensitivity is close to alarm levels. You
must turn on P132 for this field to display data at the host FACP. Turning on P132 causes all
Almost Dirty detectors to display a trouble at the panel.
Email This Report.
Allows you to email the displayed report. The size of the report may require
the system to send multiple email messages. When the report is requested, it will be sent via email
to the user who is currently logged into the system.
To find information about a specific point, click the View Point Data item on the System menu.
A screen comes up, showing the expected point number formats for each type of point. Below the
list of expected point formats is a list of card addresses and corresponding card types. Below that
are a drop-down list and an empty number field.
Use the drop-down list to select the type of point you want a report on. Next, enter the point
number, using the list of expected point number formats as a guide. Click Update to bring up the
report.
The point report that comes up is identical to what you see when you click the point as a
hyperlink. Refer to “Report Items” under “Basic Reports,” later in this publication.
Viewing System, Card, and Point Reports
Overview
Viewing TrueAlarm
Service Reports
Viewing TrueAlarm
Status Reports
Viewing Point
Summaries
Содержание SafeLINC 4020-0160
Страница 1: ...Installation Setup Operating Instructions SafeLINCTM Fire Panel Internet Interface FPII 579 349 Rev H...
Страница 2: ......
Страница 55: ...49 MIS IT Configuration Worksheet...
Страница 56: ...50 MIS IT Configuration Worksheet Continued...
Страница 57: ......