48
When you click on a Custom Label for any event, a screen comes up that summarizes the address
corresponding to that label. This section explains the details of the summary report.
Here are some of the items that may be displayed whenever a system point is shown as a
hyperlink.
Current Device.
Displays whether the device is seen correctly by the system.
Device.
The device status (Alarm, Trouble, Supervisory, No Answer, etc.).
Test State.
Shows whether the device is self-testing, and the results of a self-test.
Present Sensitivity Selected.
The percentage of a value (for example, smoke on a smoke detector)
that must be detected by the device to go into alarm.
Average Value.
The number of units of a value (for example, smoke on a smoke detector) that the
device currently detects on average.
Alarm Level.
The number of units of a value (for example, smoke on a smoke detector) that the
device needs to sense to go into alarm.
Value.
The current number of units of a value (for example, smoke on a smoke detector) that the
device is detecting.
Peak.
The highest number of units of a value (for example, smoke on a smoke detector) that the
device has detected in the past.
Trouble Threshold.
The value that the device needs to cause the display of a trouble message.
Enabled State.
Shows whether the device is enabled or disabled. Devices may be enabled or
disabled via the SafeLINC FPII.
Unverified.
System points that are not returning a value.
Basic Reports
Overview
Report Items
Содержание SafeLINC 4020-0160
Страница 1: ...Installation Setup Operating Instructions SafeLINCTM Fire Panel Internet Interface FPII 579 349 Rev H...
Страница 2: ......
Страница 55: ...49 MIS IT Configuration Worksheet...
Страница 56: ...50 MIS IT Configuration Worksheet Continued...
Страница 57: ......