15
RUI/4100 Comms or Slave Core –
This is the same trouble information that the RS232 card
normally reports. The signal line is brought into the SafeLINC FPII so that it can be monitored for
trouble reporting on the RS232 card. This line is monitored continuously during boot-up and run-
time because the RS232 is communicating to the host FACP during these times. When this trouble
is active, a trouble will be reported to the host FACP.
RAM Test –
Conducted only at boot-up and characterized by the long continuous illumination of
LED3 while the test is ensuing, this test covers the entire contents of the DRAM (both U21 and
U22) on the SafeLINC FPII to ensure that the memory integrity is intact.
FLASH Test –
Conducted only at boot-up and characterized by the long continuous illumination
of LED3 while the test is ensuing, this test covers the entire contents of the FLASH (U20) on the
SafeLINC FPII to ensure that the memory integrity is intact.
EEPROM Test -
Conducted only at boot-up and characterized by the long continuous
illumination of LED3 while the test is ensuing, this test covers the entire contents of the Serial
EEPROM (U6) on the SafeLINC FPII to ensure that the memory integrity is intact.
LED Indicators,
Continued
Interpreting LED
Indications