9-20
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Suppression
Release Device
and Point Types
Suppression release device and point types are shown in the table below. Assign the applicable
device and point types to the suppression points
before
programming hazard area information.
Refer to section
Programming Points
inside the Online Help of the 4007ES Panel Programmer
for information on programming the points.
Continued on next page
Table 9-2. Valid Device and Point Types
Point Type
Description
Valid Device Types
AutoGenerates to Following Lists:
RELSIG
Releasing
audible circuit
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SIGIAM,
NULLSIG, PS_SIGA, PS_SIGB,
MFIO_SIGA, MFIO_SIGB, MSOUND,
MSIGA, MSIGB, VNAC
L0 - Coding Group 0
L1 - Coding Group 1
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
RELISIG
NYC
investigation
bell/strobe
circuit
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SBZAM,
SAZAM, NULLSIG, PS_SIGA, PS_SIGB,
MFIO_SIGA, MFIO_SIGB, MSOUND,
MSIGA, MSIGB, VNAC
L0 - Coding Group 0
L1 - Coding Group 1
L48 - TrueAlert Zone OFF on SILENCE
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
RELVIS
Release visual
circuit
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SBZAM,
SAZAM, SIGIAM, NULLSIG, PS_SIGA,
PS_SIGB, MFIO_SIGA, MFIO_SIGB,
MSOUND, MSIGA, MSIGB, VNAC
L0 - Coding Group 0
L13 - Fire Alarm Visuals OFF on RESET
L49 - TrueAlert Zone OFF on RESET
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
RELWVIS
Releasing
warning visual
signal
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SBZAM,
SAZAM, SIGIAM, NULLSIG, PS_SIGA,
PS_SIGB, MFIO_SIGA, MFIO_SIGB,
MSOUND, MSIGA, MSIGB, VNAC
L0 - Coding Group 0
L13 - Fire Alarm Visuals OFF on RESET
L49 - TrueAlert Zone OFF on RESET
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
SSABRT
Shorted
Suppression
Agent Abort
Zone
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM, SECIAM,
MAZAM, MBZAM
SSDUMP
Shorted
Suppression
Agent Manual
Dump
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM, SECIAM,
MAZAM, MBZAM, ADRPUL, CANPUL
L18 - General Fire Alarm Monitor Zones
L30 - Alarm Verification Group 0
L61 - Coding Group 1 - Monitor Zones
L139- Local Mode Operation Points
SUPRELS
Suppression
Release Output
RELEASE, SIGA, SIGB, CHAN2A,
CHAN2B, CHAN4A, CHAN4B, PCHAN4A,
PCHAN4B, SBZAM, SIGIAM, SAZAM,
NULLSIG, PS_SIGA, PS_SIGB,
MFIO_SIGA, MFIO_SIGB
SUPRELS
(Graphic24)
Suppression
(Agent
Discharge)
Release Output
OUTPUT
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...