A-11
4007ES Panel Programmer Manual (
579-1167)
Releasing Specific Controls and Indications,
Continued
Abort Switch
Trouble during
Normal
Supervisory
Conditions
2. Configure three unused digital pseudo points to be used as two new troubles and a
supervisory point. Label them as follows (change HAZNAME to the appropriate label for
your hazard area):
3. In the
Suppression Release Wizard
that you are working on, right click the title (next to
the wizard graphic) and select
Properties
to open the
Hazard Area
.
4. Select the points tab and write down the lists assigned to
Abort Switches
and
Automatic
Release Points
.
5. Enable Manual Editing of the suppression release wizard equations.
Right click the wizard for that hazard and select
Enable Manual Edit
. Click
Yes
in the
confirmation box.
Continued on next page
IMPORTANT:
When you enable manual edit the
Suppression Release Wizard
cannot be
used to modify this hazard area.
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......