9-10
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
General
Information
After you enter a name for the floor group, click
Next
. A dialog appears, with this dialog you
can specify general information about the application.
.
Figure 9-15. Floor Above/Below Data
Specify this information as follows:
• Program #. Use this entry to specify the Custom Control user program in which this
application is to be stored. Three programs are available for user programs.
• Number of Floors. This specifies the total number of floors controlled by the floor
above/below equations.
• Control # of Floors Above. When a fire occurs, this setting determines how many
floors above the fire floor are notified.
• Control # of Floors Below. When a fire occurs, this setting determines how many
floors below the fire floor are notified.
• Type (select all that apply)
- Non-Audio. Select if using non-audio notification appliances
- Smoke. Select this option to control smoke control (damper/AHU) points
Click
Next
when you are finished.
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......