7-9
4007ES Panel Programmer Manual (
579-1167)
Point Editing for TrueAlert Device,
Continued
TrueAlert ES AV-H
Appliance Point
Editing
Use this device type to edit TrueAlert ES Audible/Visual High Candela (AV-H) appliances. The
following editing options are available for this appliance:
Table 7-7.TrueAlert ES AV-H Point Editing Options
Option
Description
Custom Label
This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label
This field is used to enter an alternative description of the appliance.
Style
Select the Style that corresponds to the appliance or device you are programming.
• Indoor.
• Available candela
options:
System Default. Selecting this option sets the candela value
to the one selected in the System Option tab.
110 candela
135 candela
185 candela
Hardware. Selecting this option sets the appliance to the
setting indicated on the appliance's configuration switch or
jumper.
Operation
Select the type of operation the appliance will signal.
General Evac.
The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other
When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.
Mounting
Only a ceiling-mounted appliance is allowed
Candela
Select the candela output of the appliance. The selection varies according to the
appliance style.
Horn Type
Broadband
Multitone
Tone
BROADBAND
BROADBAND, 520 HZ, BELL, SLOW WHOOP, SIREN,
HILO, CHIME, HARDWARE
Continued on next page.
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......