9-24
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Suppression
Release Use
Cases
Use Case #2:NYC Abort
Specific Configuration
True Alert Zone
• SIG912 is configured as RELISIG (Releasing Investigation Circuit) and has at least
one audible device from the IDNAC channel.
Abort Logic Window
• Set
NYC
Hazard Area Lists Window
• Press
Release
Investigation Points
and select
SIG912.
Table 9-4 describes actions and their corresponding responses.
Use Case #3: IRI Abort
Specific Configuration
True Alert Zone
• SIG915 is configured as RELVIS (Releasing Visual Signal) and has at least one visual
device from the IDNAC channel.
Abort Logic window
• Set
IRI Abort.
Hazard Area Lists window
• Press
Release Notification Visible NACs
and select
SIG915.
Table 9-4. NYC Abort, Actions and Responses
Action
Response
First detector is
triggered.
RELISIG turns on steady.
Second detector is
triggered.
• RELISIG turns off.
• RELWVIS turns on.
• RELSIG turns on at high cadence (March120).
Press and release the
abort switch
.
• Automatic Release Timer countdown is reset to the original value.
• RELISIG turns on steady for 90 seconds.
• RELWVIS turns off.
• RELSIG turns off.
Note:
If the abort switch is pressed and released after the second alarm while the
investigation timer is running, the investigation timer will not be reset and
will continue to countdown until it reaches zero. When the investigation
timer reaches zero, RELSIG and RELWVIS will turn back on and the
automatic release timer will begin to countdown. If the abort switch is
pressed and released again while the automatic release timer is running, a
new full cycle of investigation and automatic release delay will start.
Investigation Timer
expires
• RELISIG turns off.
• RELWVIS turns on.
• RELSIG turns on at high cadence (March120) for the full period of the Automatic
Release Timer.
• RELSIG turns on steady, RELWVIS stays on, SUPRELS NAC turns on steady
and SRP output turns on steady after the full Automatic Release Timer expires.
Continued on next page
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......