3.
If the display in LSM switches from 'Open' to 'Closed' when the
door is almost closed:
Reduce the number of magnetic plates
Move the plate further towards the centre of the frame
Make the plate smaller
4.
Close door. The display in LSM must change from 'Open' to
'Closed.' If this is not the case, the magnetic field is too weak for
the sensor. Affix another plate to the frame and repeat the test
If the magnetic field is too big (too many plates), this will cause the
sensor to overreach, so that it no longer responds
2.4.2 Functions test
The functions test verifies that the complete communication chain
from the sensors to LSM function correctly
The following tests need to be performed
ü
The locking plan is open
ü
The DoorMonitoring status is displayed in the locking plan
or
ü
The properties in the cylinder 'Door monitoring status' tab are
open
ü
The individual test results can be checked in LSM
1.
Opening the door
2.
Closing the door
3.
Rotate the cam bit once » lock. Repeat until the bolt is fully
extended, depending on the number of turns required in the lock
4.
Rotate the cam bit once » open. Repeat until the bolt is fully
withdrawn, depending on the number of turns required in the
lock
5.
Opening the door
6.
Leave the door open until the 'Door open too long' message
appears
Calibration tool
This offline cylinder test is carried out with a separate calibration tool
if the DoorMonitoring cylinder is set up or operated offline or the test
is part of an error search if statuses are incorrectly displayed or are
not displayed at all during an online test.
We recommend the calibration tool if
– The DoorMonitoring Cylinder is not networked. In such a case,
you can check status changes with the tool
– The DoorMonitoring Cylinder is being set up by one person. In
such a case, status changes cannot be checked directly in LSM
Manual
Door Monitoring Cylinder
44 / 72
SimonsVoss
2 | Initial operation