54
– Turn the
encoder to modify the first digit from 0 to 1
– Press the
click
encoder to confirm the modification and
select the next digit
– Continue in this way until the CODE (or password)
“1 2 3 4 5”
has been completed
ENTER ACCESS CODE
Code:
1 2 3 4 5
Cancel
Confirm
Fig. 148
– Press the
Confirm
button to access the boiler
“Parameter
settings”
area
Boiler parameters
Esc
Back
Parameter Index: 1
Parameter Value: 0
1--------49
Fig. 149
– The
“Parameter index”
refers to the parameter table below
– Turn the
encoder to scroll through the list of
parameters and check the value.
If the value of the selected parameter is to be modified:
– Press the
click
encoder to access the value modification
area
Boiler parameters
Esc
Back
Parameter Index: 1
Parameter Value: 0
1--------49
Fig. 150
– Press the
encoder to set the new value
– Press the
click
encoder to confirm the modification and
move on to another parameter
– Once all the display/modification commands have been
completed, press the
Esc
button to go back to the
“Main screen”
.
Thu 18 Set 2014
Zone
10:30
Menu
Mode
Off
Fig. 151
Type
No.
Description
Range
U/M
Step
Default
CONFIGURATION
PAR
01
Index showing boiler power in kW
5 = 25 (Murelle Revolution 25)
6 = 30 (Murelle Revolution 25 30)
0 .. 6
-
1
5
PAR
02
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or heating only
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
0 .. 4
-
1
0
PAR
03
Gas Type Configuration
0 = G20; 1 = G31
0 .. 2
-
1
0
PAR
04
Combustion configuration
0 = sealed chamber with combustion control
-
-
-
0
PAR
08
External sensor value correction
-5 .. +5
°C
1
0
PAR
09
Ignition fan speed
80 .. 160
RPMx25
1
128
DOMESTIC HOT WATER - HEATING
PAR
10
Boiler Antifreeze Threshold
0 .. +10
°C
1
3
PAR
11
External Sensor Antifreeze Threshold
-- = Disabled
-9 .. +5
°C
1
-2
PAR
12
Heating Curve Incline
0 .. 80
-
1
20
PAR
13
Minimum Heating Temperature Adjustment
20 .. PAR 14
°C
1
20
PAR
14
Maximum Heating Temperature Adjustment
PAR 13 .. 80
°C
1
65
PAR
15
Maximum power heating
0 .. 100
%
1
100
PAR
16
Heating Post-Circulation Time
0 .. 99
seconds
x 10
1
3
PAR
17
Heating Pump Activation Delay
0 .. 60
seconds
x 10
1
0
PAR
18
Re-ignition Delay
0 .. 60
Min
1
3