38
5.14.1 External sensor
Murelle Revolution 25
requires an outdoor probe. This is supplied
and MUST be connected because the boiler uses the outdoor
temperature detected to operate.
m
CAUTION
The boiler CANNOT FUNCTION unless the outdoor probe
is installed
.
Climatic curve
Delivery temperature
30
10
20
0
-10
-20
-30
80
90
70
60
75
65
50
40
30
20
10
0
°C
°C
K=4
K=2
K=1
K=9 K=8
K=3
K=5
K=6
K=7
External temperature
k=4
Factory settings
Fig. 69
Procedure for selecting the climatic curve
To select the preferred climatic curve:
– from the
“Main screen”
on the main control panel (MCP)
Thu 18 Set 2014
Zone
10:30
Menu
Mode
Off
Fig. 70
– Press the
Menu
button to view the
“Menu”
selection
screen
– turn the
encoder to select the
“TECHNICAL”
menu
Esc
Back
GENERAL SETTINGS [...]
INFORMATION
[...]
TECHNICAL
[...]
MENU
Fig. 71
– press the
click
encoder to access the modifiable area. The
following screen is displayed:
Cancel
Confirm
CONFIRM REQUEST
Confirm operation?
Fig. 72
– press the
Confirm
button to access the submenus
TECHNICAL
Esc
Back
State hybrid operation
[...]
Zone
heating
[...]
Ht-boiler adjust. param.
[...]
Hot water
[...]
Boiler parameters
[...]
Fig. 73
– turn the
encoder to select the
“Zone heating”
submenu
TECHNICAL
Esc
Back
Zone
heating
[...]
Ht-boiler adjust. param.
[...]
Hot water
[...]
Boiler parameters
[...]
Advanced parameters Ht
[...]
Fig. 74
– Press the
click
encoder to access the modifiable parameters
area
Zone heating
Esc
BACK
Req. from ext. TA
NO
Room probe run
YES
Room probe modul.
YES
Ext. probe modul.
YES
Weather comp.curve
4.0
Fig. 75