53
6.4
Parameter setting and display
To access the parameters menu from the
“Main screen”
:
Thu 18 Set 2014
Zone
10:30
Menu
Mode
Off
Fig. 143
– Press the
Menu
button to view the
“Menu”
selection
screen
– turn the
encoder to select the
“TECHNICAL”
menu
Esc
Back
GENERAL SETTINGS [...]
INFORMATION
[...]
TECHNICAL
[...]
MENU
Fig. 144
– press the
click
encoder to access the modifiable area. The
following screen is displayed:
Cancel
Confirm
CONFIRM REQUEST
Confirm operation?
Fig. 145
– Press the
Cancel
button to go back to the
“TECHNICAL”
menu.
– Press the
Confirm
button to access the submenus.
TECHNICAL
Esc
Back
State hybrid operation
[...]
Zone
heating
[...]
Ht-boiler adjust. param.
[...]
Hot water
[...]
Boiler parameters
[...]
Fig. 146
– Turn the
encoder to select the required submenu
– Press the
click
encoder to confirm the selected submenu
and access the modifiable parameters area.
NOTE
: The parameters below can be found in the submenu “HP-
Boiler adjustment parameters”.
Type No. Description
Range
U/M
Step
Default
P
110
ΔT ON heating
request
0
….10
°C
1
1
P
120
ΔT OFF heating
request
0
….10
°C
1
4
P
130
Outdoor probe
temperature
for boiler ON to
boost
-5
….15
°C
1
7
P
140 Time 1 boiler ON
(to support)
0
….60
min
1
20
P
150 Time 2 boiler ON
(to support)
0
….60
min
1
5
P
160
ΔT ON heating
boost request
-20
…20
°C
1
2
P
170
ΔT OFF heating
boost request
-20
…20
°C
1
1
P
180
ΔT set for heat
pump
-10
…10
°C
1
8
P
190
Time 3 boiler
ON (restart
prevented)
0
…30
min
1
3
P
510
Outdoor probe
temp. for heat
pump OFF
-15
…0
°C
1
-7
P
520 Boiler activation
to boost heating
Off/
On
-
-
On
P
530 Domestic hot
water activation
Off/
On
-
-
On
P
540 Heat pump
activation
Off/
On
-
-
On
P
550 HP maximum
limit
30
…55
°C
1
47
Time Programming
[……]
-
-
-
Once the HP-Boiler parameter setting is complete::
– Press the
Esc
button
– Turn the
encoder to select the
“Boiler parameters”
submenu
The following screen appears when the
encoder is
pressed as confirmation:
ENTER ACCESS CODE
Code:
0 0 0 0 0
Cancel
Confirm
Fig. 147