45
Type No. Fault
Solution
AL
10 Auxiliary sensor fault
- Check the hydraulic con-
figuration using "tS 0.2"
- Check the electrical con-
nection
AL
11 Gas valve modulator
disconnected
- Check the electrical con-
nection
AL
12
Domestic hot water
sensor fault in tank
mode
- Set the parameter tS 0.4
(Combustion configuration)
to 0
AL
13 Exhaust sensor (SF)
intervention
- Check the sensor is
working
- Replace the smoke probe
AL
14 Exhaust sensor (SF)
fault
- Replace the smoke probe
- Check the electrical con-
nection of the smoke probe
- Contact the Technical
Assistance Centre
AL
15 Fan check cable dis-
connected
- Check the connection
cable between the fan and
the board
AL
18 Condensate level fault
- Check for any clogging in
the pipe which takes the
condensate to the siphon
- Check that the siphon is
not clogged
AL
28
Maximum number of
consecutive resets
reached (6)
- Wait 1 hour and try un-
blocking the board again
- Contact the Technical
Assistance Centre
AL
30
Return sensor fault
(boiler sensor fault for
T models)
- Replace the return probe
- Check parameters
- Contact the Technical
Assistance Centre
AL
37 Fault due to low net-
work voltage
- Check the voltage
- Contact your network
provider
AL
40 Incorrect supply fre-
quency detected
- Contact your network
provider
AL
41 Flame loss more than
6 consecutive times
- Check the ignition/detec-
tion electrode
- Check the gas supply
(open valve)
- Check mains gas pressure
AL
42 Button fault
- Check that buttons are
working
AL
43 Open Therm communi-
cation fault
- Check the OT electric
connection
AL
44 No flame valve opening
time sum anomaly
- Check for the presence
of water hammer on the
hot water system and, if
present, mount a water
hammer arrestor
- Check for any abnormal
requests on the room
thermostat
- Contact the Technical
Assistance Centre
AL
56
Lock for
∆T
delivery/
return over max limit
(open vent)
- Contact the Technical
Assistance Centre
AL
57
Lock for flow temper-
ature (FT) check (open
vent)
- Contact the Technical
Assistance Centre
AL
62 Self-calibrating proce-
dure is required
- Carry out the self-cali-
brating procedure (see the
specific section)
AL
72 Incorrect positioning of
the delivery sensor
- Check delivery sensor
operation and position
AL
74 Second delivery sensor
fault
- Check second delivery
sensor operation and
position
AL
77
EV2 SGV current max/
min absolute limits
error
- Check gas valve and board
AL
78 EV2 SGV current upper
limit error
- Check gas valve and board
AL
79 EV2 SGV current lower
limit error
- Check gas valve and board
Type No. Fault
Solution
AL
80
Fault on the valve
control logic line/valve
cable damaged
- Check gas valve and board
AL
81 Lockout due combus-
tion during start-up
- Check for blockage in flue
- Check air diaphragm (for
BF models)
- Check gas calibration
- Bleed the air from the gas
circuit
AL
82
Block due to numerous
combustion control
failures
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
AL
83 Irregular combustion
(temporary error)
- Check for blockage in flue
- Check air diaphragm (for
BF models)
- Check gas calibration
AL
84
Flow rate reduced for
(presumed) low pres-
sure on mains gas
- Check gas flow rate
AL
88 Internal error (board
component protection)
- Check the board is working
- Replace board
AL
89 Unstable combustion
feedback signal error
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
AL
90 Combustion set cannot
be reached error
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
ALL
91 Gas valve out of range
- Recalibrate the gas valve
AL
92
System has reached
maximum air cor-
rection error (at the
minimum flow rate)
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
AL
93 Combustion set cannot
be reached error
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
AL
95 Flame signal micro
interruptions error
- Check electrode
- Check board
- Check electric power
supply
- Check gas calibration
AL
96 Lockout due to flue
(exhaust) blockage
- Check for blockage in flue
- Check the smoke outlet
and electrode position (not
touching the burner)
AL
98 SW error, board start-
up
- Contact the Technical
Assistance Centre
AL
99 General board error
- Contact the Technical
Assistance Centre
-
-
Frequent relief valve
intervention
- Check circuit pressure
- Check expansion vessel
-
-
Limited production of
domestic hot water
- Check the diverter valve
- Check that plate heat
exchanger is clean
- Check domestic hot water
circuit valve
Содержание MIA-30
Страница 3: ...3...
Страница 8: ...8...
Страница 14: ...14...
Страница 23: ...23...
Страница 48: ...48 9 EXPLODED VIEWS Frame...
Страница 49: ...49 Hydraulic assembly...
Страница 50: ...50 Exchanger Combustion...
Страница 51: ...51 Control panel...
Страница 52: ...52 Additional components...
Страница 53: ...53...