56
Figure 1
– Connection of condensate discharge pipe to internal soil and vent stack.
Note – Check manufacturer’s instructions to see if an air break is required.
Key
1
Boiler
2
Visible air break
3
75 mm trap
4
Visible air break and trap not required if there is a trap with a minimum condensate seal
of 75 mm incorporated into the boiler
5
Soil and vent stack
6
Invert
7
450 mm minimum up to three storeys
8
Minimum internal diameter 19 mm
1
2
5
4
8
3
7
6
October 2018 Issue 1.0
Содержание MIA-30
Страница 3: ...3...
Страница 8: ...8...
Страница 14: ...14...
Страница 23: ...23...
Страница 48: ...48 9 EXPLODED VIEWS Frame...
Страница 49: ...49 Hydraulic assembly...
Страница 50: ...50 Exchanger Combustion...
Страница 51: ...51 Control panel...
Страница 52: ...52 Additional components...
Страница 53: ...53...