20
5.7
Sensors
The sensors installed have the following characteristics:
– Dual sensor (thermal safety/output) NTC R25°C; 10kΩ
β25°-85°C: 3435
– domestic hot water sensor NTC R25°C; 10kΩ β25°-85°C:
3435
– External temperature sensor NTC R25°C; 10kΩ β25°-85°C:
3435
Correspondence of Temperature Detected/Resistance
Examples of reading:
TR=75°C → R=1925Ω
TR=80°C → R=1669Ω.
TR
0°C 1°C 2°C 3°C 4°C 5°C 6°C 7°C 8°C 9°C
Resistance R (Ω)
0°C 27279
17959
12090
8313
5828
4161
3021
2229
1669
1266
973
26135
17245
11634
8016
5630
4026
2928
2164
1622
1232
25044
16563
11199
7731
5440
3897
2839
2101
1577
1199
24004
15912
10781
7458
5258
3773
2753
2040
1534
1168
23014
15289
10382
7196
5082
3653
2669
1982
1491
1137
22069
14694
9999
6944
4913
3538
2589
1925
1451
1108
21168
14126
9633
6702
4751
3426
2512
1870
1411
1079
20309
13582
9281
6470
4595
3319
2437
1817
1373
1051
19489
13062
8945
6247
4444
3216
2365
1766
1336
1024
18706
12565
8622
6033
4300
3116
2296
1717
1300
998
10°C
20°C
30°C
40°C
50°C
60°C
70°C
80°C
90°C
100°C
5.8
Expansion vessel
The expansion vessel installed on the boilers has the following
characteristics:
Description
U/M
MIA-30
Total capacity
l
7,0
Prefilling pressure
kPa
100
bar
1,0
Useful capacity
l
4,45
Maximum system
content (*)
l
110
(*) Conditions of:
Average operating temperature 70°C (with high tempera-
ture system 80/60°C)
Start temperature at system filling 10°C.
m
CAUTION
– For systems with water content exceeding the
maximum system content (as indicated in the ta-
ble) an additional expansion vessel must be fitted.
– The difference in height between the relief valve
and the highest point of the system cannot exceed
6 metres. If the difference is greater than 6 me-
tres, increase the prefilling pressure of the expan-
sion vessel and the system when cold by 0.1 bar
for each meter increase.
5.9
Circulation pump
The flow-head performance curve available for the heating
system is shown in the graph below.
RESIDUAL HEAD (mbar)
0
0
800
1000
1200
600
400
200
100
200
300
400
500
600
30
FLOW (l/h)
Fig. 13
m
CAUTION
The appliance is equipped with a by-pass which en-
sures water circulation in the boiler when thermo-
static valves are used in the system. The heating sys-
tem design should incorporate a room thermostat.
Thermostatic radiator valves fitted to all radiators
except the room where the room thermostat is fit-
ted. Properties with floor areas exceeding 150squre
metres should be zoned.
Содержание MIA-30
Страница 3: ...3...
Страница 8: ...8...
Страница 14: ...14...
Страница 23: ...23...
Страница 48: ...48 9 EXPLODED VIEWS Frame...
Страница 49: ...49 Hydraulic assembly...
Страница 50: ...50 Exchanger Combustion...
Страница 51: ...51 Control panel...
Страница 52: ...52 Additional components...
Страница 53: ...53...