![SILENT KNIGHT INTELLIKNIGHT 5820XL Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/silent-knight/intelliknight-5820xl/intelliknight-5820xl_installation-manual_1271114076.webp)
IntelliKnight 5820XL Installation Manual
5-8
151137
5.8
Relay Module Installation
The information in this section applies to Model SD500-ARM Relay Modules. See Section
5.10.2 for information on how to use the on-board dipswitch to select an address for the
module.
5.8.1
Electrical Specifications
The following is electrical rating information for SD500-ARM relay modules.
Relay Ratings
30 VDC @ 2.0 A Resistive
30 VDC @ 1.0 A Inductive (.6PF)
30 VDC @ 0.6 A (0.35PF) Pilot Duty—Light duty low voltage S.W.
120 VAC @ 0.6 A (0.35PF) Pilot Duty
Connect to power limited sources only.
Note: PF = Power Factor.
5.8.2
Wiring
Wire relay modules to the panel or to the 5815XL as shown in Figure 5-9.
Figure 5-9 Relay Module Connection to the FACP (Class B)
Control Panel
or
5815XL
SD500-ARM
Supervised
Power Limited
Содержание INTELLIKNIGHT 5820XL
Страница 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Страница 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Страница 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Страница 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Страница 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Страница 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Страница 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Страница 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Страница 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...