IntelliKnight 5820XL Installation Manual
3-10
151137
U Change clock display format (12-hour with AM/PM by default).
7.5.6.4
U Enable/disable day/night sensitivity (disabled by default).
7.5.4
U Select holiday schedule (up to 18 days) if installation is using day/night
sensitivity.
7.5.5
U Set up reporting accounts.
7.5.1
U Select options for phone lines.
7.5.2
U Select system-wide response to trouble conditions, if desired.
7.5.3
U Select system-wide cadence patterns for special conditions (fire drill, Aux1
and Aux2 alarms) if desired.
7.5.3
U Customize banner message (message that displays on LCD in normal
mode) if desired.
7.5.8
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart).
You can change options selected by JumpStart, if necessary and further customize input point
options.
U Program type of switch (manual pull, fire drill, and so on), if necessary.
(JumpStart assigns all switches as Manual Pull type.)
7.4
U If the installation includes duct detectors, program detector type.
(JumpStart does not distinguish duct detectors from ordinary smoke
detectors.)
7.4
U Assign a name (or description) to the point.
7.4.3.1
U Assign input points to zones, if necessary. (JumpStart assigns all input
points to Zone 1.)
7.4
Zone Configuration
U Add the zone to the system if it does not already exist. (Zone 1 created by
JumpStart.)
7.2.2
U Program a name (or description) for the zone.
7.2.1.1
U Select alarm delay options (detection characteristics) for zone.
7.2.1.2
U Select heat detector trip temperature and/or smoke sensitivity level for
photoelectric smoke detectors. (JumpStart selects 150(F for heat detectors
and Low sensitivity for smoke detectors.)
7.2.1.2
Output Point Configuration
Conventional notification circuits (circuits 1-6):
U Enable circuits used for notification appliances through programming, if
necessary. (JumpStart enables circuits 1-6 as Notification.)
7.3.1
Conventional relay circuits (circuits 7-8):
U Select options for relay circuits, if desired. Note: Relay circuits will always
output continuously (constant pattern), even if assigned to an Output Group
that uses a different output pattern.
7.3.1
Auxiliary power circuits (circuits 1-6):
U Enable any circuit used for auxiliary power devices through programming.
7.4
U Select type of power (door holder, constant, or resettable)
7.4
Task
See Sec.
(for more info.)
Содержание INTELLIKNIGHT 5820XL
Страница 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Страница 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Страница 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Страница 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Страница 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Страница 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Страница 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Страница 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Страница 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...